Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05382
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/19/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
01/27/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) LABEL DISCONNECTS, UNITS AND PANELS 2) PROTECT SEAL TITE FROM SHARP METAL EDGES 3) WE HAVE MULTI-POLE TERMINATIONS AT GROUND LUG 4) MAINTAIN WORKING CLEARANCES IN FRONT OF NEW PANEL 5) PLEASE HAVE ELECTRICIAN PRESENT TO OPEN ENERGIZED PANEL 6) WHERE IS 200 AMP BREAKER AS PER PLANS |