Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/27/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) LABEL DISCONNECTS, UNITS AND PANELS 2) PROTECT SEAL TITE FROM SHARP METAL EDGES 3) WE HAVE MULTI-POLE TERMINATIONS AT GROUND LUG 4) MAINTAIN WORKING CLEARANCES IN FRONT OF NEW PANEL 5) PLEASE HAVE ELECTRICIAN PRESENT TO OPEN ENERGIZED PANEL 6) WHERE IS 200 AMP BREAKER AS PER PLANS |