Permit: T03CM05371

Parcel: 116124830

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM05371

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) ABS DWV THRU ROOF OK. 2) PEX OK. 3) CLOSET FLANGES OK. 4) WASTE AND OVERFLOWS OK. 5) OK TO COVER ALL AREAS.
03/01/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) SEE NOT #2 FROM 2/25/04 2) SEE NOT #4 FROM 2/25/04 HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP INCLUDES LAVATORIES 3) REPLACE N/H BAND WITH SOLVENT WELD COUPLING 4) CLOSET FLANGES TO BE SECURE IN THE FLOOR 5) WATER TEST OK-NEED TO SEE CONNECTIONS AT W & O 6) YARD WATER OK 7) OK TO COVER
02/25/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE CLEANOUT FOR KITCHEN SINKS AND WASHER 2) MUST USE DRAINAGE FITTING FOR HORIZONTAL VENT AT KITCHEN OR RAISE VENT TO 42" A.F.F. 3) MUST REVISE APPROVED PLAN SHOWING WATER SERVICE SPLITING LINES TO 3/4" AND VTR CHANGE TO 2" IN PLUMBING WALL 4) MUST USE A L-SWEEP ON TRAP ARM FOR A WASHER 5) RETEST SYSTEM
02/24/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) INSTALL PER PLAN OR HAVE PLAN CITY APPROVED AND REVISED TO SHOW INSTALLATION