Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM05371
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) ABS DWV THRU ROOF OK. 2) PEX OK. 3) CLOSET FLANGES OK. 4) WASTE AND OVERFLOWS OK. 5) OK TO COVER ALL AREAS. | |
| 03/01/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) SEE NOT #2 FROM 2/25/04 2) SEE NOT #4 FROM 2/25/04 HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP INCLUDES LAVATORIES 3) REPLACE N/H BAND WITH SOLVENT WELD COUPLING 4) CLOSET FLANGES TO BE SECURE IN THE FLOOR 5) WATER TEST OK-NEED TO SEE CONNECTIONS AT W & O 6) YARD WATER OK 7) OK TO COVER | |
| 02/25/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) MUST PROVIDE CLEANOUT FOR KITCHEN SINKS AND WASHER 2) MUST USE DRAINAGE FITTING FOR HORIZONTAL VENT AT KITCHEN OR RAISE VENT TO 42" A.F.F. 3) MUST REVISE APPROVED PLAN SHOWING WATER SERVICE SPLITING LINES TO 3/4" AND VTR CHANGE TO 2" IN PLUMBING WALL 4) MUST USE A L-SWEEP ON TRAP ARM FOR A WASHER 5) RETEST SYSTEM | |
| 02/24/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) INSTALL PER PLAN OR HAVE PLAN CITY APPROVED AND REVISED TO SHOW INSTALLATION |