Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM05345

Parcel: 13615040A

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM05345

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/25/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/PARTIAL
03040-1) WATER TEST FROMMETER THRU 2" BACKFLOW DEVIDE TO BLD # 1 & 2 OK PENDING REVISED CITY APPROVED DRAWING SHOWING METER & BACKFLOW SIZE & LOCATION
03055-AIR TEST FOR 2-WAY CLEANOUT OK
1) NEED VERIFICATION OF GRADE ON SEWER WITH DATE AFTER 8/25/04
2) SEWER FROM BLD 1 & 2 TO BE COMPLETE PIPED AND HAVE TEST ON ENTIRE LINE WITH 1/8" PER FOOT MINIMUM FALL
08/16/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
08/02/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) 6 PSI AIR TEST ON UNDERGROUND WASTE AND VENT ONLY AS SHOWN ON PAGE 15.1 OF CITY APPROVED PLAN OK 2) WILL NEED TO SEE TEST FROM STUB THRU 2-WAY CLEANOUTS AT TIME OF SITE SEWER INSPECTION