Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM05345
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2004 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
08/25/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/PARTIAL 03040-1) WATER TEST FROMMETER THRU 2" BACKFLOW DEVIDE TO BLD # 1 & 2 OK PENDING REVISED CITY APPROVED DRAWING SHOWING METER & BACKFLOW SIZE & LOCATION 03055-AIR TEST FOR 2-WAY CLEANOUT OK 1) NEED VERIFICATION OF GRADE ON SEWER WITH DATE AFTER 8/25/04 2) SEWER FROM BLD 1 & 2 TO BE COMPLETE PIPED AND HAVE TEST ON ENTIRE LINE WITH 1/8" PER FOOT MINIMUM FALL |
|
08/16/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
08/02/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 1) 6 PSI AIR TEST ON UNDERGROUND WASTE AND VENT ONLY AS SHOWN ON PAGE 15.1 OF CITY APPROVED PLAN OK 2) WILL NEED TO SEE TEST FROM STUB THRU 2-WAY CLEANOUTS AT TIME OF SITE SEWER INSPECTION |