Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/16/2004 EXT METAL CLIPS/EXT SHEATHING Approved
05/25/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) CHECK FOR H2.5'S AT INTERMEDIATE, AT REAR PORCH 2) TIE WALL TO ROOF, LIVING ROOM-MASTER BEDROOM 3) CHECK WHAT IS # SYMBOL ON TRUSS DRAWINGS 4) TRUSS DRAWINGS FOR FAMILY ROOM, TRUSS GOES OUT TO PORCH CHECK FOR DRAWING BEARING PTS 5) 2" C. WATER ON PLAN INSTALLED, OR TO BURY, OR COVER, 3/4" METER HAVE PLAN CHANGED
04/22/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*/ 1) ROOF TO LEDGER CONNECTIONS THRU-OUT OK
04/20/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000*/ 1) PLAN DOESN'T HAVE A CROSS SECTION 2) JOIST SIZE NOT SHOWN 3) LEDGER JOIST WALL CONNECTION NOT SHOWN 4) HANGER SIZE NOT SHOWN 5) STUD SIZE NOT SHOWN, SPACING 6) SHEAR WALL, OR BRACE WALL, NO SCHEDULE, NAILING PLYWOOD SIZE, TYPE