Permit: T03CM05317

Parcel: 140373940


Addresses:

6225 E STONECHAT DR

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/18/2004 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*SENT TO TEP ON 02/19/04AM
02/17/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*/ 1) UFER GROUND NOT INSTALLED IN PANEL 2) COVER OPENING AT DEAD FRONT
01/26/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*/ 1) UFER TO SHORT NOT GROUNDED AT PANEL 2) RISER CLAMP MISSING BOLT