Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/30/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/25/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* |
| 03/23/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) ELECTRICAL NOT PROTECTED PER PLAN 2) SECURE ROMEX WITHIN 8" FROM BOX 3) REPAIR RIPPED DUCT 4) ROMEX NOT ALLOWED TO BE NAILED ON IT'S SIDE |
| 03/19/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BLOCK MECHANICAL IN LIVING ROOM AND LAUNDRY 2) NO TEST ON 2ND FLOOR DWV'S 3) PROVIDE DAMPERS EXHAUST FANS 4) ELECTRIC INCOMPLETE TO FAN IN BATHROOM 5) TRUSS OVERFRAME NOT PER PLAN 14/SD4 6) CHECK NAIL PROTECTION |
| 02/02/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* LATH NOT INSTALLED |