Permit: T03CM05310

Parcel: 115043890


Addresses:

1140 N 2ND AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM05310

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/14/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SUBMIT REVISION FOR EXTRA WEIGHT OF AIR HANDLER IN ATTIC
04/29/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) AIR HANDLER IN ATTIC, HAS A U.L. LABEL MARK THE SPACE NEXT TO THE HEAT STRIP THAT'S INSIDE 2) YOU NEED A ACCESS HOLE TO SERVICE THE UNIT, ALSO A WORKING PLATFORM AND WALK WAY IF THE ACCESS HOLE IS NOT WITHIN WORKING DISTANCE OF THE UNIT, FRAMING MUST BE STRONG ENOUGH TO SUPPORT A LIVE LOAD 3) YOU NEED AN OVER FLOW PAN AND SECONDARY DRAIN TO OUTSIDE 4) YOU WILL NEED A DISCONNECT, FUSE PROTECTION THEIR OR AT SERVICE 5) WHEN LABEL IS MARKED CIRCUIT AMPACITY AND FUSE SIZE CAN BE DETERMINED 6) BLOCK AROUND YOUR MECH DUCT OPENINGS IN EACH ROOM AT CEILING 7) PLAN CALLS FOR ALL EXHAUST FAN IN BATHROOM 8) YOU NEED TO ADDRESS MANU FRAMING ITEMS, INCLUDING THE EXTRA WEIGHT OF ATTIC UNIT MAINTENCE LIVE LOAD EXT. 9) YOU HAVE A GALVANIZED 1" PIPE TAPPED INTO SEWER VENT VENTS OPEN TO ATTIC 10) NO ELECTRIC PAGE IN PLAN SET 11) RANGE HOOD/EXHAUST ?