Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T03CM05308
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2004 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
04/20/2004 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection 0999*/ PARALLELING OFF OF 400 AMP BREAKER FOR TWO 200 AMP PANEL BOARDS IN VIOLATION OF ART. 240 - MUST TERMINATE IN SAME EQUIPMENT, 200 AMP PANELBOARD FUSED AT 400 AMP. MUST HAVE CITY APPROVED REVISION. |