Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 04/23/2004 |
ELECTRIC - TEMP POWER FOR TEST |
|
Approved |
|
| 04/20/2004 |
ELECTRIC - TEMP POWER FOR TEST |
|
Denied |
IVRS - Inspection 0999*/ PARALLELING OFF OF 400 AMP BREAKER FOR TWO 200 AMP PANEL BOARDS IN VIOLATION OF ART. 240 - MUST TERMINATE IN SAME EQUIPMENT, 200 AMP PANELBOARD FUSED AT 400 AMP. MUST HAVE CITY APPROVED REVISION. |