Permit: T03CM05307

Parcel: 110151150


Addresses:

5518 E GLENN ST #A


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05307

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE 2) OK FOR C OF O
11/12/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
11/07/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) UNIT C-SECTION OF VENT CONNECTOR NOT LONG ENOUGH FOR PROPER CONNECTION. UNIT D-EXTEND REFER LINE INSULATION TO COVER ENTIRE PIPE IN FURNACE CLOSET. UNIT A-FURNACE IS MISSING A SERVICE PANEL. UNIT B-REMOVE SCREEN FROM DRYER VENT. UNIT C- REPAIR DOUBLE WALL VENT PIPE. INNER LINER OF VENT HAS SEPERATED FROM OUTER WALL ON ROOF WHERE VENT CAP IS ATTACHED. RECALL FOR INSPECTION