Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR FINAL C OF O. |
| 03/10/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) FAN COIL OVERFUSED. 15 AMP IS MAXIMUM 2) PROVIDE 20 AMP FUSES IN CONDENSOR DISCONNECT 3) PROVIDE SCREEN IN ALL OUTSIDE AIR INTAKES 4) REPAIR DAMAGED INSULATION. CAULK HOLES IN WALL |