Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05289
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2004 | ELECTRIC - INTERMEDIATE | Approved | ||
03/03/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/11/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/NEED ACCURATE CITY APPROVED REVISED DRAWING FOR SERVICE NO. 2. NEED GROUNDING BUSHINGS AND BOND JUMPER. NEED JUMPER AT ENDS OF CONDUIT ENCLOSING GROUND EL. CORD. WIRE BEND RADIUS EXCEEDED. HAVE AIC RATINGS. | |
01/21/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ WALLS APPROVED |