Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM05288
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR FINAL C OF O. | |
03/10/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) FANI COIL OVERFUSED. 15 AMP IS MAX. 2) REPAIR DMAGED INSULATION AND SEAMS 3) SECURE RETURN DUCT IN CLOSET 4) SUPPORT OR SECURE REFER LINES TO WALL AT CONDENSOR. PROVIDE PROTECTION ON EXPOSED CONTROL WIRING TO CONDENSOR 5) PERMANENTLY LABEL DISCONNECT OR CONDENSOR WITH ADDRESS | |
03/02/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ provide clear access to fan coils. | |
02/09/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO SHEET ROCK SOFFITS |