Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/09/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 03/03/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 02/19/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ PLEASE HAVE LETTER STAMPED AND APPROVED BY C.O.T. PLANS EXIMNER. NEED GROUNDING BUSHING AT RISER. |
| 02/11/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ WILL NEED REVISED DRAWING ON NEW SERVICE ENTRANCE #2. SHOW GUTTER, TYPE OF TERMINATION AND WIRE SIZES. NEED GROUNDING BUSHINGS AND BONDING JUMPER AT GUTTER CONDUIT TERMINATION. NEED GROUNDING BUSHINGS AND BOND JUMPERS AT BOTH ENDS OF CONDUIT ENCLOSING GROUND EL. CORD. NEED CORRECT AIC RATING. WIRE BOND RADIUS AT ONE PHASE IN GUTTER EXCEEDS MIN. STANDARDS. |
| 01/20/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK WALLS EXCEPT OVER UN POURED FLOOR |