Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/18/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CANNOT LOCATE 220 VOLT WIRES ON PLAN KITCHEN SOUTHWALL 2) INSTALL ROMEX CONNECTORS METAL ELECTRIC BOXES 3) CANNOT LOCATE SMOKE DETECTORS HALL FIRST FLOOR 4) WHAT IS ELECTRIC LOPPED IN WALK IN CLOSET FOR ? (NOT SHOWN ON PLANS) 5) BLOCK 3 SIDES MECHANICAL DUCTS AT PENETRATIONS CEILING |
|
| 01/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST COMPLETE ALL LATH INSTALLATION PRIOR TO REQUESTING INTERMEDIATE INSPECTIONS 2) MOVE WIRES AWAY FROM FLUE PIPES AND SECURE 3) DWV TEST TO GO THROUGH ROOF 4) STOPPED INSPECTION 5) COMPLETE ALL TO PLAN/CODE-RECALL |