Permit: T03CM05281

Parcel: 117084010


Addresses:

307 W 19TH ST

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
06/09/2004 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*/ 1) COMPLETE WALL CANNOT BE HIGHER THAN 12' FROM FINISH FLOOR
06/02/2004 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*/ 1) PARTIAL UP TO 8' AND LINTEL HEIGHT
05/26/2004 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*/ 1) 1ST 48" LIFT OK TO GROUT 2) LAY BLOCK TO 8' HEIGHT, INSTALL REBAR 3) RECALL INSPECTION BEFORE GROUTING
04/30/2004 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) WINDOWS NOT INSTALLED SOUTH AND WEST WALLS 2) HORIZONTAL REBAR REQUIRED UNDER WINDOW OPENINGS 3) ROUGH OPENING BEGINS AT 2'-8" ABOVE FINISHED FLOOR ELEVATION
04/12/2004 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection 0000*/ 1) LAY BLOCK TO 48" HEIGHT 2) INSTALL VERTICAL REBAR ( OVERLAPPING 30 BAR DIAMETERS) 20" MINIMUM ON #5 REBAR 3) INSTALL HORIZ REBAR WHERE INDICATED 4) CALL FOR 1ST LIFT 01020 (DO NOT GROUT) 5) MUST USE AGGREGATE IN GROUT