Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 03/03/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 02/09/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) APPROVED PLOT PLAN SHOWS 4'-2" BETWEEN HOUSE AND NEW ADDITION 3'-6" EXISTS 2) NEED VERIFICATION OF EAST PROPERTY LINE SET PROPERTY PINS AND PULL STRING LINE TO VERIFY 1' SET BACK 3) DETAIL D2 CALLS FOR #4 DOWELS AT 24" ON CENTER SPACING VERTICALS AT WALL OPENINGS (3 LOCATIONS) 4) PLAN CALLS FOR #5 VERTICAL REBAR AT 48" CENTER AND AT ALL CORNERS, ENDS, JAMBS, INTERSECTIONS, BOTH SIDES OF CONTROL JOINTS 5) STOPPED INSPECTION |