Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM05276
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL C/O | |
| 12/23/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/NEED TO SEE 35 AMP BREAKERS. NEED TO SIGN PERMIT CARD | |
| 12/22/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/30 AMP CIRCUIT TO A/C EQUIPMENT NOT ADEQUATE. #10 WIRE NOT ADEQUATE |
|
| 12/20/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PERMANENTLY IDENTIFY A/C UNIT W/ADDRESS 2)INSTALL FRESH AIR INTAKE, CONDENSATSDRAIN 3)SECURE ELECTRICAL CONDUITS ON ROOF 4)PRIVIDE SCREEN IN T-TOPS. 5)EXTEND ANY SEWER VENTS WITHIN 10' OF FRESH AIR INTAKE. |