Permit: T03CM05267

Parcel: 116010940

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
02/12/2004 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection 0000*
02/11/2004 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection 0000* 1ST LIFT
02/10/2004 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) 20" LAP REQUIRED AT VERTICALS
02/09/2004 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) GROUTED PRIOR TO INSPECTION 2) NOTES: POOR DESIGN FOR COLUMNS 3) DESIGN SHOULD INCLUDE 4 VERTICALS AND TIES AT 24" ON CENTER
02/05/2004 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection 0999*/ 1) NO PLAN ON SITE 2) NOTE: FIRST LIFT EXCEEDS MAXIMUM ALLOWABLE HEIGHT