Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O. |
| 12/04/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ IDENTIFY PRIMARY AND SECONDARY DRAIN LINES. SECURE DRAIN LINE TO UNISRUT. FINISH SEALING DUCT JOINTS. LABEL UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY. |
| 12/03/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE SECONDARY DRAIN PANS UNDER A/C UNITS. EXTEND CONDENSATE DRAIN TO SINK. 2) LABEL UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY. 3) FINISH EXHAUST TERMINATION. 4) SEAL DUCT JOINTS. |