Permit: T03CM05254

Parcel: 14108521C

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/05/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O.
12/04/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ IDENTIFY PRIMARY AND SECONDARY DRAIN LINES. SECURE DRAIN LINE TO UNISRUT. FINISH SEALING DUCT JOINTS. LABEL UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY.
12/03/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE SECONDARY DRAIN PANS UNDER A/C UNITS. EXTEND CONDENSATE DRAIN TO SINK. 2) LABEL UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY. 3) FINISH EXHAUST TERMINATION. 4) SEAL DUCT JOINTS.