Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM05214

Parcel: 13331159U


Addresses:

8840 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05214

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR C OF O.
11/19/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PAINT EXPOSED PVC WITH LATEX PAINT. 2) LABEL DATA PLATES WITH PROPER HEAT STRIPS INSTALLED AND FUSE ACCORDINGLY. 3) PERMANENTLY LABEL EQUIPMENT WITH ADDRESS AND UNIT NUMBER. 4) CONDENSATE CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. DISCHARGE TO AN APPROVED LOCATION. 5) THREE NEW A/C UNITS INSTALLED WITHOUT PERMITS. OBTAIN NECESSARY PERMITS. 6) CAP OFF TEES IN SEWER VENT. RECALL FOR FINAL.
11/14/2003 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*/ OK FOR CEILING TILE. PROVIDE ACCESS TO ROOF FOR FINAL INSPECTION.
11/13/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ NO PLANS ON SITE. RECALL FOR INSPECTION.