11/21/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ OK FOR C OF O. | |
11/19/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) PAINT EXPOSED PVC WITH LATEX PAINT. 2) LABEL DATA PLATES WITH PROPER HEAT STRIPS INSTALLED AND FUSE ACCORDINGLY. 3) PERMANENTLY LABEL EQUIPMENT WITH ADDRESS AND UNIT NUMBER. 4) CONDENSATE CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. DISCHARGE TO AN APPROVED LOCATION. 5) THREE NEW A/C UNITS INSTALLED WITHOUT PERMITS. OBTAIN NECESSARY PERMITS. 6) CAP OFF TEES IN SEWER VENT. RECALL FOR FINAL. | |
11/14/2003 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ OK FOR CEILING TILE. PROVIDE ACCESS TO ROOF FOR FINAL INSPECTION. | |
11/13/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ NO PLANS ON SITE. RECALL FOR INSPECTION. |