Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T03CM05209
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* LIGHT POLE BASES OK | |
08/03/2004 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :FINISH INSTALLING #5'S @ CENTRAL JOINTS VERTICLES INCOLUMNS REQUIRE MIN 1 1/2" SPACING - PLEASE MOVE OUT BEFORE POURING #OF VERT IN MASONRY REQUIRE 18" LONG SPLICE - BLOCK OUT FOOTING & DO NOT POUR THIS AREA MATS HAVE NOT BEEN PLACED IN F-3 FOOTINGS HAVE SPECIAL INSP CALL ME THIS PM TO VERIFY F3 MATS & CENTRAL JOINT VERTS ARE IN PLACE |