Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 01/29/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 01/27/2004 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) POST ADDRESS # VISIBLE FROM STREET 2) PLAN CALLS FOR 12" X 8" CONCRETE STEM OVER EXISTING 3) RASTRA WALL SYSTEM HAS VERTS AT 15" CENTER SPACING 4) MINIMUM 3" CONCRETE ENCASEMENT REBAR WITH CONCRETE 5) INSTALL GRADE PINS REAR FOOTINGS FOR MINIMUM 8" THICKNESS AND POST FTGS, ALSO 12" THICKNESS 6) INTERIOR FTGS INCOMPLETE 7) ONE INTERIOR FTG (POST) INCORRECT LOCATION |