Permit: T03CM05181

Parcel: 13419042C


Addresses:

7160 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/07/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/18/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ MUST HAVE A PERMANENT GRADE OR FINISHED FLOOR IN FRONT OF C.T. JUNCTION BOX. THE WIDTH OF THE EQUIPMENT AND AT LEAST 4'6" OUT - PREFERABLY 5' OUT. MUST HAVE ACURATE CITY APPROVED REVISIONS TO THE ONE LINE DIAG FOR THE ADDED JUNCTION BOXES - IN GROUND AND IN WALL - CONDUITS AND SIZES ETC. UPON APPROVAL OF ABOVE, AN ELECTRICAL FINAL WILL BE APPROVED. NOT FOR C OF O OR POWER. AN UNIMPROVED UNIT.
05/11/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ RECESSED LIGHTS AT LOADING DOCKWILL NEED ACCESS PANEL FOR BOX.
05/10/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SUPPORT M/C CABLE WITHIN 12" OF FIXTURE 2) FILL UNUSED OPENINGS