Permit: T03CM05176

Parcel: 120070300


Addresses:

145 W AJO WY

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/20/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) PLBG FINAL OK. 2) OK FOR C OF O.
05/14/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) C.O. ON TRAP ARM MUST BE A DIRECTIONAL FITTING AND MUST BE ABOVE THE CENTER LINE OF DRAIN. 2) MUST STRAP DOWN EXPANSION TANK FOR WTR HTR. 3) PROVIDE VACUUM BREAKER ON SERVICE SINK FAUCET. 4) T&P DRAIN FOR WTR HTR HAS BACKPITCH. 5) PLEASE PROVIDE TEST AND CERTIFICATION OF BACKFLOW PREVENTOR
05/12/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) sink requires a c.o. 2) WTR CLOSET REQUIRES AN OPEN FRONT SEAT. 3) MUST PROVIDE EXPANSION TANK FOR WTR HTR.