Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/20/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 04/01/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
1) WASTE AND VENT SYSTEM IS OK. 2) WTR DISTRIBUTION IS OK IN PLBG WALLS ONLY. OK FOR DRYWALL. 3) THERE IS STILL ½" COPPER TOUCHING METAL STUDS OVER REFER. |
| 03/30/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 03/29/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) CAN ONLY SERVE 2 FIXTURES ON A ½" COLD. 2) SOIL WTR TEST IS OK. |
| 03/25/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST PROVIDE MIN. 3" VENT THRU ROOF. VENT MUST EQUAL AGGREGATE CROSS SECTIONAL AREA OF REQUIRED BLDG. SEWER. SEE SEC 904.1, 94 UPC. 2) NO TEST ON SYSTEM. 3) LOTS OF LOOSE WTR LINES IN WALL. 4) MUST PAY RE-INSPECTION FEE PRIOR TO NEXT INSP. 5) SEE NOTE 1 FROM PREVIOUS INSP. |