Date Description Inspector Results Comments
02/24/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/09/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK WALLS 1) PLEASE FINISH #5 AS PREVIOUS.
01/07/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) FILL UNUSED OPENING IN BOXES 2) TIGHTEN LOOSE FITTINGS-SET SCREWS AND LOCK NUTS 3) FINISH INSTALLATION OF "P" RINGS 4) UNCOVER CONDUIT UNDER GROUND TO VERIFY TAPE WRAPING 5) HAVE PLANS REVISED FOR ALL DELETIONS, ADDITIONS AND RELOCATIONS OF OUTLETS