Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05171
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/24/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
01/09/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS 1) PLEASE FINISH #5 AS PREVIOUS. | |
01/07/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) FILL UNUSED OPENING IN BOXES 2) TIGHTEN LOOSE FITTINGS-SET SCREWS AND LOCK NUTS 3) FINISH INSTALLATION OF "P" RINGS 4) UNCOVER CONDUIT UNDER GROUND TO VERIFY TAPE WRAPING 5) HAVE PLANS REVISED FOR ALL DELETIONS, ADDITIONS AND RELOCATIONS OF OUTLETS |