Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH. 1) THHN IS NOT A SUPPORT METHOD. DO NOT SUPPORT OFF?? OTHER WIRING METHODS | |
| 03/28/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) COMPLETE # 3 OF PREVIOUS INSPECTION ( 3/7/05) OK TO LATH | |
| 03/11/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio PHONE # NOT A WORKING NUMBER-LEFT MESSAGE ON OFFICE MACHINE. 1) NO WORK PROGRESS- A REFEE PER ADMIN CODES IS BEING ACCESSED. THIS IS THE 4TH INSPECTION. |
|
| 03/10/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SNAP IN FITTING TO BE INTO BOXES 2) WHERE ARE THE REST OF THE FIXTURES AS PER PLANS 3) FINISH #3 OF PREVIOUS INSPECTION. | |
| 03/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE WRITE-UP FOR 3/7/5 |
|
| 03/07/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) WE HAVE BOX OVER FILL AT PANCAKE BOXES 2) UNCOVER COLUMNS TO INSPECT WIRING 3) SUPPORT NM CABLE WITHIN 12" OF CANS.4) AN APPROVED CONNECTOR IS NEEDED FOR BOXES. 5) METAL BOXES TO BE GROUNDED. 6) NO APPROVED PLANS ON SITE. |