Permit: T03CM05162

Parcel: 12613018A


Addresses:

4544 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05162

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O.
12/09/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) CONDENSATE DRAIN HAS BACK PITCH HORIZONTAL SECTION ON ROOF. PROVIDE A BLOCK AND CLAMP 2) MAKE UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE DISCONNECT ACCORDINGLY 3) PROVIDE AN OUTSIDE AIR INTAKE AS PER PLANS 4) PROVIDE A VENT ON CONDENSATE DRAIN DOWNSTREAM OF THE TRAP. CORRECT DRAIN LINE TO LAV. TAIL PIECE 5) PERMANENTLY LABEL A/C UNIT WITH ADDRESS 6) RECALL FOR INSPECTION