Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM05162
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. OK FOR C OF O. | |
12/09/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) CONDENSATE DRAIN HAS BACK PITCH HORIZONTAL SECTION ON ROOF. PROVIDE A BLOCK AND CLAMP 2) MAKE UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE DISCONNECT ACCORDINGLY 3) PROVIDE AN OUTSIDE AIR INTAKE AS PER PLANS 4) PROVIDE A VENT ON CONDENSATE DRAIN DOWNSTREAM OF THE TRAP. CORRECT DRAIN LINE TO LAV. TAIL PIECE 5) PERMANENTLY LABEL A/C UNIT WITH ADDRESS 6) RECALL FOR INSPECTION |