Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM05157
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2004 | FRAMING | Approved | ||
11/16/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE PACHO METER TEST TO JUSTIFY REQUIRED REINFORCEMENT AT CMU WALL 2) BASEMENT OUTLETS SHALL BE GFI 3) RUNS P & R LINE AT W/H 6" FROM SLAB MINIMUM 24" MAX 4) PROVIDE GUARD RAIL AT STAIRWELL 5) RELOCATE ELECTRIC ? DISCONNECT FROM BEHIND A/C 6) PROVIDE SHUT OFF AT GAS LINE IN FRONT OF UNION |