Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T03CM05153
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/29/2004 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :*/ 1) NEED ALL BONDING PER PLAN 2) NEED LABELING FOR HEAT STRIP 3) NEED BONDING FOR STEEL BLDG, AND STRUCTUAL STEEL (EXPOSED) 4) SEE LAST INSPECTION | |
| 07/27/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) KITCHEN ISLAND GFCI OUTLET LEFT ON SINK IRC 3801.9.4 2) WHITE WIRES CANNOT BE HOT IN PANEL COLOR CODE RED |