Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/05/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK WALLS TO CLOSE 2) REVISE PANEL SCHEDULE AND TOTAL LOAD CALC'S TO INCLUDE PANEL "C" |
| 12/16/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MAINTAIN WORKING CLEARANCE FOR SUB PANEL "C" 110.26 2) SUPPORT NM CABLE DOWN WALL AS PER CODE 3) PROTECT CABLES IN STUDS WITH APPROVED PLATES 4) SUPPORT CABLES ABOVE PANEL 5) #8 WIRE TO HAVE PROTECTION WHERE EXPOSED 250.64 6) PLEASE FINISH ITEM #2, 3 AND 4 OF PREVIOUS INSPECTION |
| 12/10/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*/ THE FOLLOWING NEED CLARIFICATION: 1) THE WIRING METHOD USED IS NON-METALLIC SHEATHED CABLE (ROMEX) THE PLAN SPECS OF SHEET E.1 SPECIFY THE USE OF APPROVED RACEWAY WITH WIRE DRAWN INTO CONDUIT. THE ENGINEER/ARCHITECT MUST ISSUE HIS LETTER APPROVING THE CHANGE IN WIRING METHOD 2) THE SUB-PANEL AND CALC'S DO NOT PROVIDE FOR THE CONDENSING UNIT CIRCUIT 3) THE WATER HEATER CIRCUIT HAS BEEN CHANGED TO TWO POLE 30 AMP. TO ACCOMODATE THE HEATER. 4) FEEDER CABLE FOR PANEL "C" MUST BE INCLUDED IN WIRING METHOD CHANGE 5) GROUNDING IS NOT PER PLAN |