Permit: T03CM05129

Parcel: 111070240


Addresses:

3333 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/19/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/05/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS TO CLOSE 2) REVISE PANEL SCHEDULE AND TOTAL LOAD CALC'S TO INCLUDE PANEL "C"
12/16/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) MAINTAIN WORKING CLEARANCE FOR SUB PANEL "C" 110.26 2) SUPPORT NM CABLE DOWN WALL AS PER CODE 3) PROTECT CABLES IN STUDS WITH APPROVED PLATES 4) SUPPORT CABLES ABOVE PANEL 5) #8 WIRE TO HAVE PROTECTION WHERE EXPOSED 250.64 6) PLEASE FINISH ITEM #2, 3 AND 4 OF PREVIOUS INSPECTION
12/10/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*/ THE FOLLOWING NEED CLARIFICATION: 1) THE WIRING METHOD USED IS NON-METALLIC SHEATHED CABLE (ROMEX) THE PLAN SPECS OF SHEET E.1 SPECIFY THE USE OF APPROVED RACEWAY WITH WIRE DRAWN INTO CONDUIT. THE ENGINEER/ARCHITECT MUST ISSUE HIS LETTER APPROVING THE CHANGE IN WIRING METHOD 2) THE SUB-PANEL AND CALC'S DO NOT PROVIDE FOR THE CONDENSING UNIT CIRCUIT 3) THE WATER HEATER CIRCUIT HAS BEEN CHANGED TO TWO POLE 30 AMP. TO ACCOMODATE THE HEATER. 4) FEEDER CABLE FOR PANEL "C" MUST BE INCLUDED IN WIRING METHOD CHANGE 5) GROUNDING IS NOT PER PLAN