Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM05120

Parcel: 13419042D


Addresses:

7220 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T03CM05120

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
07/29/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
07/26/2004 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :60 PSI AIR TEST ON 2 1/2 TO 2 FROM MOTOR TO ROOFTOP UNITS AND HANGING SPACE OK
SUPPORT PIPING ON ROOF AT CORRECT INTERIORS WITH APPROVED METHODS
EXPOSE CLOSET RING IN MENS REST ROOM
07/09/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/ 1) INSTALL PIPING PER APPROVED PLAN OR PROVIDE REVISED CITY APPROVED PLAN 2) SUPPORT ALL PIPING AT CORRECT INTERVALS WITH APPROVED METHODS 3) PROVIDE BONDING OF BLDG GAS PIPING
07/07/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/ 1) PROVIDE REVISED ROUGH SOIL CITY APPROVED 2) PROVIDE CITY APPROVD REVISED PLAN FOR H2O PIPING 3) PROVIDE 60 PSI AIR TEST ON WELDED GAS PIPING AND INSTALL PER PLAN WITH PROPERLY SIZED GAS FLEXES