Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2004 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :*/ 1) REVISED PLAN ON SITE 2) NO PROBLEM FOR TEMP C OF O |
| 04/19/2004 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 5 PSI AIR TEST ON UNDERSLAB UP TO REVENT HEIGHT OK. PENDING CITY APPROVAL OF REVISED 8½ X 11 WITH INITIAL FROM ME. 4/16/04 |
| 04/16/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) DBL FIXTURE FITTING IS REQUIRED AT BACK TO BACK FLOOR DRAINS. IF DBL SANITARY TEE IS USED BARREL IS REQUIRED TO BE 2 PIPE SIZES LARGER THAN DRAIN ARMS. 2) LONG RAPINS FITTINGS ARE NOT REQUIRED AT C.O. LOCATIONS OR BLAKE TEES. 3) SUPPLY DRAIN FOR SK SINK. |
| 04/09/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ INSTALL UNDERGROUND PIPING PER PLAN. |