Permit: T03CM05120

Parcel: 13419042D


Addresses:

7220 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/08/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/ 1) REVISED PLAN ON SITE 2) NO PROBLEM FOR TEMP C OF O
04/19/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 5 PSI AIR TEST ON UNDERSLAB UP TO REVENT HEIGHT OK. PENDING CITY APPROVAL OF REVISED 8½ X 11 WITH INITIAL FROM ME. 4/16/04
04/16/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) DBL FIXTURE FITTING IS REQUIRED AT BACK TO BACK FLOOR DRAINS. IF DBL SANITARY TEE IS USED BARREL IS REQUIRED TO BE 2 PIPE SIZES LARGER THAN DRAIN ARMS. 2) LONG RAPINS FITTINGS ARE NOT REQUIRED AT C.O. LOCATIONS OR BLAKE TEES. 3) SUPPLY DRAIN FOR SK SINK.
04/09/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ INSTALL UNDERGROUND PIPING PER PLAN.