Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05079
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS, CEILING | |
07/16/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio/ 1) DID NOT PAY REFEE |
|
06/22/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ no compliance with last insp. no corrections made. a re-insp fee is assessd please pay refee at 201 n. stone before future insp. |
|
04/12/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) RECEPTACLE BOXES MUST HAVE AT LEAST 2' SEPERATION FROM OTHER OUTLET BOXES IN FIREWALL OR ISOLATED BY STUDS IN WALL. BOX MUST BE FIRERATED PER FIRE WALL RATING CHECK WITH BLDG INSP. FOR INFO. 2) SERVICE DISCONNECT IN NEED OF REPAIR OR RE-SUPPORT, USE APPROVED FITTINGS WHERE LINE LOAD CONDUCTORS EXIT AND ENTER. CHECK FOR CLEARANCE SO DOOR OPEN 90o ON DISCONNECT TO RIGHT. |