Permit: T03CM05077

Parcel: 138150970


Addresses:

212 E MEDINA RD


Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Permit Number - T03CM05077

Inspection Description - SHEET ROCK NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/24/2003 SHEET ROCK NAILING Approved IVRS - Inspection 0000*