Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T03CM05077
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
11/26/2003 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) PHD HOLDOWN AT FRONT ENTRY WINDOW AND REAR WINDOW SHALL BE NAILED TO TWO FULL LENGTH STUDS 2) POSITIVE CONNECTION REQUIRED AT FRONT PORCH BEAM AT SHORT 2-X'S 3) CHECK FOR BANG PLATES THRU-OUT 4) 4 X 4 POST W/PC44 AND CB44 REQUIRED AT FRONT PORCH COLUMN SEE SECTION D & C SHEET 3 5) DOUBLE KING STUDS REQUIRED AT OPENINGS OVER 48" | |
11/21/2003 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) EAST WINDOW KING STUD NOT CLIPPED 2) PATIO DOOR KING STUD NOT CLIPPED 3) WEST SHEAR PANEL NOT NAILED 4) DOUBLE KING STUDS REQUIRED AT GARAGE 5/8 5) SHEAR WALL ANCHOR BOLTS MUST BE 5/8", 7/8" 6) DOUBLE KING STUDS REQUIRED AT ALL WINDOWS OVER 4' WIDE SEE 5/8 7) MANY AREAS OF ROOF PANELS NOT NAILED TO TRUSSES |