Permit: T03CM05056

Parcel: 132191150


Addresses:

2185 E IRVINGTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM05056

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ SMOKE ALARMS, WHERE IS PERFORATED TUBE? INSIDE DUCT? SHOULD GO SIDE TO SIDE. WHERE IS SPEC SHEET SHIPPED WITH ALARM?
04/07/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ ACE HARDWARE - SMOKE ALARMS LOCATE IN RETURN AIR DUCTS - NOT SUPPLY. INSULATE 90o ELLS IN SUPPLY ABOVE CEILING TILES.
04/01/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ OK TO COVER SUITES 110, 120, 130, 140
03/26/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ TEMP C OF O OK.
03/25/2004 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*/ PROVIDE MIN. 48" PER FT SLOPE ON ALL CONDENSATE DRAIN LINES. SEE SEC. 307.1 2000 IMC. PROVIDE DUCT SMOKE DETECTORS. CANNOT HAVE EXPOSED COMBUSTABLES IN A PLENIUM CEILING.
03/15/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
03/02/2004 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) SUPPLY DROPS DOWN FROM CURB TO REG. BOXES. PROVIDE 1" STRAPS AS NESCESSARY. 2) SUPPLY SPIRAL PIPE, ABOVE CEILING GRID - NEED TO INSULATE DUCT 3/4" DUCT WRAP (BELOW BUILDING BLANKET). 3) OK TO ROCK HARD LIDS.