Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/12/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ SMOKE ALARMS, WHERE IS PERFORATED TUBE? INSIDE DUCT? SHOULD GO SIDE TO SIDE. WHERE IS SPEC SHEET SHIPPED WITH ALARM? |
| 04/07/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ ACE HARDWARE - SMOKE ALARMS LOCATE IN RETURN AIR DUCTS - NOT SUPPLY. INSULATE 90o ELLS IN SUPPLY ABOVE CEILING TILES. |
| 04/01/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ OK TO COVER SUITES 110, 120, 130, 140 |
| 03/26/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ TEMP C OF O OK. |
| 03/25/2004 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*/ PROVIDE MIN. 48" PER FT SLOPE ON ALL CONDENSATE DRAIN LINES. SEE SEC. 307.1 2000 IMC. PROVIDE DUCT SMOKE DETECTORS. CANNOT HAVE EXPOSED COMBUSTABLES IN A PLENIUM CEILING. |
| 03/15/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 03/02/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SUPPLY DROPS DOWN FROM CURB TO REG. BOXES. PROVIDE 1" STRAPS AS NESCESSARY. 2) SUPPLY SPIRAL PIPE, ABOVE CEILING GRID - NEED TO INSULATE DUCT 3/4" DUCT WRAP (BELOW BUILDING BLANKET). 3) OK TO ROCK HARD LIDS. |