Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM05056
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/08/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ WTR TEST THRU ROOF SUITE 110 AND 120 WASTE AND VENT OK. H20 70 PSI IN WALL OK. | |
03/05/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ WASTE AND VENT WATER TEST THRU ROOF ROOMS 132 AND 142 OK. H2O PRESSURE TEST 70 PSI OK. WILL NEED LETTER FROM ARCHETECT OR ENGINEER DELETING COLD WATER INSULATION OR HAVE IT INSTALLED. | |
03/01/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
02/27/2004 | PLUMBING - INTERMEDIATE | Partial Approval | 1) WATER TEST ON WASTE AND VENT THRU ROOF AND WATER IN WALL AND OVERHEAD APPROVED FOR NORTH WEST RESTROOM AREA. P3-1 REVISED DRAWING SHOWS 2 1/2 FLOOR CLEAN OUT THIS WILL NEED TO BE ADDED PER PLAN OR REVISED ON PLAN AND DELETED | |
02/26/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) MUST PROVIDE A HANGER EVERY 4' FOR HORIZONTAL 2" VENT 2) MUST PAROVIDE INSOLATORS FOR COPPER DROPS INTO PLUMBING WALL |