Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM05056
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
04/16/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK SERVICE. COMPLETE INSTALLATION OF DISCONNECTS FOR WTR HTRS. | |
04/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) INSTALL DISCONNECT SWITCH FOR WTR HTRS, OR LOCKNUT DEVICE ON BREAKER. 2) SCRAPE OFF ENAMEL BEHIND GROUND LUG IN GUTTER, INSTALL LARGER BOLT TO HOLD LUG - LUG LOOSE. | |
04/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) SERVICE EQUIPMENT COVERED AND TAPED. PAINTERS SPRAYING WALL AREA AROUND SERVICE EQUIPMENT 2) TEMP POWER MUST BE APPROVED UNDER T.I. PERMIT | |
03/30/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ INSPECTIONS TO BE CALLED IN PER T.I. ACCOUNT # - CONTR. REQUESTED TEMP C OF O. | |
03/26/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |