Permit: T03CM05055

Parcel: 10603066A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/24/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/22/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ HAVE CONTR. ON SITE TO REMOVE COVERS. X-FORMER ENERGIZED. 791-5550 EXT. 1136.
06/04/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 112½ KUA TRANSFORMER - NEUTRAL NOT TIED TO GROUNDING ELECTRODE CONDUCTOR - NEED A MAIN BONDING JUMP. 2) J-BOX IN X-RAY ROOM - ALL ENTRY CONTAINING CONDUCTORS LARGER THAN #4 NEED BUSHINGS. 3) WIRING INCOMPLETE, NEED X-RAY MACHINE HOOKED-UP ITS ON PERMIT. SCRAPE PAINT BEHIND GROUND LUG. 4) X RAY DISCONNECT NEED BUSHINGS ON CONNECTORS WIRING INCOMPLETE SCRAPE PAINT BEHIND LUG.
05/28/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ OK TEMP C OF O 2ND FLOOR - 1) CHECK EM. LIGHTING - 2ND FLOOR DOES NOT LIGHT. 2) X-RAY MACHINE NOT COMPLETE. 3) LABEL PANEL IN SCHEDULE. 4) PLATE AND DEAD END CONDUCTORS FOR CONTROL J-BOX. 5) CABEL X-RAY DISCONNECT.