Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL C OF O | |
| 03/25/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) FIRE DAMPERS ACCESS DOORS OBSTRUCTED BY T-BAR CEILING. PLEASE LABEL ACCESS TO FIRE DAMPERS ON CEILING PANELS WITH MINIMUM 1/2" HIGH LETTERS 2) NEED TO TEST FAN SHUT DOWN WHEN SMOKE DETECTORS ARE IN ALARM 3) 350 AMP FUSES TO LARGE FOR CHILLER. MAX FUSE SIZE IS 300 AMP, SEE DATA PLATE ON CHILLER 4) SHORTEN LENGTH OF CONDENSATE PIPE OVER MOP SINK AND PROVIDE AN ELBOW |