Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T03CM05033
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2005 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :*RELOCATE ELEC CONDUIT BLOCKING FIRE DAMPER ACCESS. PROVIDE BREAKAWAY JOINTS ON DUCT MATE CONNECTIONS PROVIDE A TEST ON ALL CHILLED & HOT WATER PIPING . AN AIR TEST WILL BE REQUIRED ON ALL INSULATED PIPING OK TO PROCEED W/GRID | |
11/03/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/DISCUSSED FIRE DAMPER ISSUES. PARTIAL SUSPENDED ROUGH DUCT. OK TO INSULATE |