Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T03CM05033
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2004 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
10/06/2004 | PLUMBING - YARD WTR LINE/TEST | Cancelled | IVRS - Ri canceled | |
07/12/2004 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*/ 1) FROM METERS THRU 2-BACKFLOW DEVICES INTO 3" H20 TO BLDG STUBBED UP 5' FROM BLDG 70 PSI AIR TEST OK 2) NEED TO SEE TIE INTO BLDG AT FUTURE | |
07/08/2004 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :*/ 1) UES FITTINGS TO MAKE CHANGE OF DIRECTION 2) ACCESS TO PLANS IS NOT POSSIBLE | |
06/29/2004 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :*/ 4" CHILLED WTR SUPPLY AND RETURN UNDERGROUND ONLY FROM CHILLER TO AIR HANDLER ROOM. 100 PSI AIR TEST OK PER INITIALED DRAWING IN TRAILER. |