Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
IVRS - Inspection :* |
| 10/06/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Cancelled |
IVRS - Ri canceled |
| 07/12/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection :*/ 1) FROM METERS THRU 2-BACKFLOW DEVICES INTO 3" H20 TO BLDG STUBBED UP 5' FROM BLDG 70 PSI AIR TEST OK 2) NEED TO SEE TIE INTO BLDG AT FUTURE |
| 07/08/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) UES FITTINGS TO MAKE CHANGE OF DIRECTION 2) ACCESS TO PLANS IS NOT POSSIBLE |
| 06/29/2004 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection :*/ 4" CHILLED WTR SUPPLY AND RETURN UNDERGROUND ONLY FROM CHILLER TO AIR HANDLER ROOM. 100 PSI AIR TEST OK PER INITIALED DRAWING IN TRAILER. |