Permit: T03CM05033

Parcel: 13629003A


Addresses:

8155 E POINCIANA DR


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T03CM05033

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2004 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
10/06/2004 PLUMBING - YARD WTR LINE/TEST Cancelled IVRS - Ri canceled
07/12/2004 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*/ 1) FROM METERS THRU 2-BACKFLOW DEVICES INTO 3" H20 TO BLDG STUBBED UP 5' FROM BLDG 70 PSI AIR TEST OK 2) NEED TO SEE TIE INTO BLDG AT FUTURE
07/08/2004 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*/ 1) UES FITTINGS TO MAKE CHANGE OF DIRECTION 2) ACCESS TO PLANS IS NOT POSSIBLE
06/29/2004 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*/ 4" CHILLED WTR SUPPLY AND RETURN UNDERGROUND ONLY FROM CHILLER TO AIR HANDLER ROOM. 100 PSI AIR TEST OK PER INITIALED DRAWING IN TRAILER.