Permit: T03CM05033

Parcel: 13629003A


Addresses:

8155 E POINCIANA DR


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM05033

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/WATER TEST WASTE & VENT THRU ROOF FOR EXTERIOR DRINKING FOUNTAIN AT SOUTH WEST CORNER ADD 1/2" H2O SUPPLY FOR SAME TO PSI AIR TEST OK
10/20/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
10/07/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)HAVE ARCHITECH PROVIDE DETAIL DRAWINGS FOR EXTERIOR DRINKING FOUNTAIN P-6 PRIOR TO INSPECTION 2)FINAL CONNECTION TO BLDG SERVICE 3" IS OK
10/06/2004 PLUMBING - ROUGH, SOIL Cancelled IVRS - Ri canceled
08/10/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) PRE-SLAB AT AIR HANDLING ROOM 122 OK
07/27/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*PARTIAL APPROVAL. WATER TEST ON WASTE VENT FOR REROUTE OF 4" WASTE IN MENS SHOWER 113 AND WOMENS RESTROOM 114 BECAUSE OF FOOTINGS. OK.
06/21/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) WATER TEST ON 4" BW AND 4" BLDG DRAIN THRU BLDG TO 2-WAY CLEANOUT AND CAPPED JUST PRIOR TO BACKWATER VALVE AREA OK 2) 6" SITE SEWER FROM MANHOLE STA 0 + 00 TO STA 0 + 90 AND STA 1 + 55 INSTALLED PER PLAN 3) AIR TEST AT LATER DATE 4) THIS SEWER WILL REQUIRE VERIFICATION OF GRADE BY ENGINEER STAMPED 5) THIS SEWER MAY REQUIRE CERTIFICATE OF COMPLIANCE FROM ADEQ. 6) WILL NEED TO SEE HCS CONNECTIONS FOR BACKWATER VALVE AND 4" BLDG DRAIN 7) MAN HOLE WILL REQUIRE ? BUILD UP
06/15/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 3" BW FROM INITIALED AT SWOOP DOWN STREAM OF SHOWER WOMENS LOCKER 115 BACK UP STREAM TO 3-2" P-8'S OK.
06/08/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/07/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 4" BW AND 4" BLD DRAIN PER INITIALED DRAWING IN CONSTRUCTION TRAILER WTR TEST OK. 1) PLEASE VERIFY RIM ELEVATIONS OF MANHOLE UPSTREAM AS TO WHY ONLY 1 BLD DRAIN REQUIRES BACKWTR VALVE.