Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ PLBG FINAL IS OK. OK FOR C OF O. |
| 03/22/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 03/19/2004 |
PLUMBING - FINAL |
|
Denied |
1) MUST SOLDER FITTINGS FOR T & P DRAIN 2) MUST SNAP OFF SET SCREWS FOR H.B. VACCUM BREAKERS |
| 03/15/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST PROVIDE VACUUM BREAKERS ON ALL HOSE BIBS. 2) KITCHEN SINK C.O. MUST BE ABOVE HORIZONTAL WASTE. 3) MUST REMOVE FLEX LINE IN T&P DRAIN. 4) MUST PROVIDE EXPANSION TANK ON WTR HTRS OR PROVIDE PRV WITH BYPASS. |