Permit: T03CM05025

Parcel: 104092230

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/14/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
04/12/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ PROGRESS.
04/07/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) BE SURE TO PUT FIBER/PLASTIC BUSHINGS ON BOTH ENDS OF OFF SET NIPPLE CONNECTING METER CAN TO TERM BOX 3) YOU WILL BE REQUIRED TO BOND PANEL 'B' GROUND TO COLD WATER PIPE, SPRINKLER PIPE, AND GAS PIPE ( IF AVAILABLE IN RESTAURANT )