Permit: T03CM05005

Parcel: 136360870


Addresses:

7740 E WINNEPEG DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/13/2004 FRAMING Approved IVRS - Inspection :*
12/09/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THERE CAN BE NO SCREWS PEENTRATING THE DRYER DUCT
2) NEED FHA STRAP ON BOTTOM WALL PLATE BEHIND TOILET TO PROTECT PIPE
3) NEED BANG (PROTECTION PLATE) ON STUD TO PROTECT WIRE AT NORTH EAST CORNER OF NORTH EAST ROOM, SOUTH WEST CORNER OF SOUTHWEST ROOM AND TOP WALL PLATE IN CLOSET
12/07/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO INULATION OR SHEET ROCK UNTIL ELECTRIC AND MECHANICAL INTERMEDIATES AND FRAME PASS
12/06/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) GAS AND WATER BOND WIRE MUST BE BAR #4 WIRE
11/30/2004 FRAMING Denied 1). H2.5 CLIP RAFTERS IN N.E. ROOM ON NORTHEND 2). ADD FHA STRAP, FULLY NAILED, TO TOP PLATE AT HOME RUNS. 3) ADD RSP4 STUD CLIPS AT TOP & BOTTOM PLATES ON NORTH WALL 4) SHIM HEADERS & TRIMMERS 5) PATIO DOOR HEADER IS NOT PER PLAN-PRESENTLY VERY UNDERSIZED. 6) FIRE BLOCK BETWEEN NORTH WALL TOP PLATE & EXISTING SLUMP BLOCK WALL 7) BOND GAS & WATER LINES TO PANEL. NOTE: FRAME DOES NOT PASS INSPECTION UNTIL ALL INTERMEDIATE INSPECTIONS PASS
11/23/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/20/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/11/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) FRAME DOES NOT GET INSPECTED UNTIL ALL INTERMEDIATE INSPECTIONS PASS. 2) ROOF NAIL INSPECTION CAN NOT BE DONE BECAUSE THE SHEATHING IS COVERED. 3) EXTERIOR SHEATHING IS INCOMPLETE. 4) ROOF FRAME IS INCOMPLETE AT EAST AND WEST ENDS.