Permit: T03CM05000

Parcel: 140373820


Addresses:

7060 S PLOVER CT

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/16/2004 FRAMING Approved IVRS - Inspection 0000*
03/08/2004 FRAMING Partial Approval IVRS - Inspection 0000*
03/05/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) NO TEST ON DWV'S 2) PLUMBING OUT OF WALL AT LAUNDRY ROOM 3) WATER LINES MUST BE 12" AWAY FROM CAN LIGHTS 4) TEST AT 7 PSI, 10 PSI REQUIRED 5) SUPPORT AB'S THROUGHOUT 6) ATTIC ACCESS NOT ACCESSIBLE
03/04/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) PLUMBING OUT OF WALL AT LAUNDRY 2) WIRE IN CONTACT WITH W/H FLUE 3) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT FLUES 4) ATTIC ACCESS RESTRICTED 5) SECURE DWV'S
03/04/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED ON SITE
03/01/2004 FRAMING Denied IVRS - Inspection 0935*/ 1) GAS TEST AT 0 PSI 2) NO TEST ON DWV'S 3) REVISE PLUMBING PLAN TO SHOW CHICAGO LOOP 4) PLASTIC WATER LINES MUST BE 12" AWAY FROM CAN LIGHTS 5) NOTHING DONE FROM LAST INSPECTIONS 6) REFEE
02/27/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) MISSING ONE EAVE VENT 2) COMPLY WITH WCPC INSTRUCTIONS 3) FRONT ENTRY EAST NOT LATHED 4) GROUND EXTERIOR METAL BOX SOUTH WEST CORNER 5) NO TEST ON DWV'S 6) NO TEST ON GAS LINE 7) SEE LAST INSPECTION 8) STOPPED INSP. HAVE TRADES WALK HOUSE AND RECALL WHEN READY, NEXT FAILURE WILL RESULT IN A REFEE
02/26/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE AN APPROVED DETAIL FOR CHICAGO LOOP AT KITCHEN ISLAND APPROVED BY CITY OF TUCSON 2) NO TEST ON DWV'S 3) GAS PRESSURE TEST AT ZERO 4) WATER LINES MUST BE 12" AWAY FROM CAN LIGHTS 5) STOPPED INSPECTION, HAVE TRADES AND SUPERVISOR WALK HOUSE BEFORE RECALL