Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM04984
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/15/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC WORK ON ROOF NOT FINISHED 2) BOND WATER |
|
08/11/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL OPEN KO'S AT BELL BOX 2) BOND BOTH ENDS OF EMT WITH #2 BONDING WATER 3) INSTALL GROUNDING ELECTRODE SYSTEM AT BLDG AND AT TRANSFORMER 4) SEAL OPEN KO AT PANEL HH 5) PROVIDE PANEL SCHEDULE 6) FINISH LOAD SIDE WIRING AT ALL DISCONNECTS 7) LAND GROUNDING ELECTRODE CONDUCTOR AT TRANSFORMER DIRECTLY TO XO 8) INSTALL INSULATED BUSHING AT ALL CONDUCTORS #4 OR LARGER CONDUITS 9) FINISH WIRING AT CAR WASH 10) 4 SQ MISSING COVER ABOVE OPEN ENTRY 11) ROOF NOT FINISHED |