Permit: T03CM04982

Parcel: 131070650

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM04982

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/11/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ALL FAN COILS ISOLATE COPPER LINES FROM SCRAPING ON KNOCKOUTS AND BE SURE ALL FILTERS ARE INSTALLED
2) TAPE ENDS OF WHITE WIRE-BLACK IN DISCONNECTS
3) IU15 NOT FUSED CORRECTLY
4) CONTROL BOXES FOR FAN COILS BLOCKING DATA PLATES
5) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY
6) PROVIDE DUCT SMOKE DETECTORS AS PER PLANS